KYN61-40.5 35kV high voltage switchgear metal-clad removable AC metal enclosed switch equipment
Gengeral
This product conforms to: GB3906-2006< the exchange of 3~35KV AC metal enclosed switchgear equipment >, GB/T11022-2011< high-voltage switchgear and controlgear standards common technical requirements>, IEC60298:1990
Model Instruction

Normal Use Condition
3.1 Environment temperature:-15 ℃~+40 ℃;
3.2 Height above sea level: not more than 1000m ;
3.3 Air Relative humidity:daily average ≤95% monthly average≤90%
3.4 Earthquake magnitude ≤8
3.5 Places not corrosive or flammable gas, water vapor and other obvious pollution.
Note: beyond the normal use conditions, the user can consult with the manufacturer.
Major Technical Parameters
|
Name |
Unit |
Data |
|
|
Rated Voltage |
kV |
40.5 |
|
|
Rated Current |
A |
1250,1600,2000,(2500) |
|
|
1min Power frequency withstand voltage |
kV |
95 |
|
|
rated lightning impulse withstand voltage |
kV |
185 |
|
|
Auxiliary circuit, control circuit Power frequency withstand voltage |
V/1min |
2000 |
|
|
Rated Frequency |
Hz |
50 |
|
|
Rated short circuit breaking current |
kA |
20,25,31.5 |
|
|
Rated short-time tolerant voltage/Rated short circuit duration |
kA/4s |
20,25,31.5 |
|
|
Rated peak Withstand current |
kA |
50,63,80 |
|
|
Rated short-circuit current |
kA |
50,63,80 |
|
|
Control circuit rated voltage |
V |
DC:110 ,220 ;AC:110 ,220 |
|
|
Protection level |
Switchgear enclosure |
IP3X |
|
|
Compartment (door open) |
IP2X |
||
Structure Characteristics
The switchgear equipment has cable incoming and outgoing wire, cable line overhead line, bus tie, isolation, voltage transformer, arrester and so on a wiring scheme. The switchgear equipment with heat shrinkable insulation material and epoxy coated with insulating process, optimization of the electrode shape, the cabinet body structure is very compact. The main circuit adopts insulated bus, the adjacent cabinet bus casing separated, can effectively prevent the spread of the incident, and to her mistress line to the auxiliary supporting role. Cable room is equipped with a current transformer, grounding switch, the ample space conditions for a plurality of cable connection. In military vehicles, circuit breaker, grounding switch and after the cabinet door is provided with a part to prevent misoperation mechanical interlocking device, "five prevention "Function is complete, safe and reliable.
Schematic Diagram Of The Structure Of The Switchgear Equipment
A. Twice instrument room
B. Handcart room
C. Busbar room
D. Cable room
- Valve
- Circuit breaker handcart
- Twice plug
- The main bus
- Busbar bushing
- Earthing switch
- Contact box
- cable connection
- Current transformer
- Pressure release device

Order Notice
The following technical information should be provided for the user's order:
- Single line system diagram of a main wiring scheme
- Model and specification of main busbar
- Configuration function requirements
- Beyond the requirements of the use of environmental conditions
- Other special requirements