Electrical Ring Main Unit

Electrical Ring Main Unit

XGN2-10 Case-style Fixed Metal-Enclosed Ring main unit (Switchgear) is mainly used as reception and distribution of power supply of 3.6, 7.2 and 12KV, 3Phase AC, 50Hz in indoor system. It is specially applied to cases where frequent operations are needed. The switchgear goes in accordance with State Standard GB3906 and International Standard IEC298 and has strict “five prevention” lock function.
Send Inquiry
Description
Technical Parameters

XGN2 Case-style Fixed Metal-Enclosed Ring Main Unit

 

Generalization

 

XGN2-10 Case-style Fixed Metal-Enclosed Ring main unit (Switchgear) is mainly used as reception and distribution of power supply of 3.6, 7.2 and 12KV, 3Phase AC, 50Hz in indoor system. It is specially applied to cases where frequent operations are needed. The switchgear goes in accordance with State Standard GB3906 and International Standard IEC298 and has strict "five prevention" lock function.

 

The main switch applies ZN28A-12 segmental type vacuum breaker with Cd10 electromagnetic operational mechanics, CT8/CT19A (B) spring operational mechanics, ZN28-12 series integral vacuum breaker (with CD17 Electromagnetic Operational mechanics, CT17/CT19 spring operational mechanics) or applies ZN63-12(VS1) vacuum circuit breaker. Isolation switch applies GN30-10 rotating style and GN22-10 high current isolation switch.

product-488-239
MODEL

 

Conditions for use

 

Environment temperature: -25℃ to +40℃

Relative humidity: daily average ≤95% monthly average≤90%

Height above sea level: ≤1000m

No fire, explosion danger, serious pollution, chemical erosion or severe quake.

Earthquake magnitude ≤8

 

Major technical parameters

 

Major technical parameters of Switchgear (table 1)

 

No.

Name

Unit

Data

1

Rated Voltage

KV

3,6,10

2

Rated Current

A

630,1000,1250,1600,

2000,2500,3150

3

Rated Frequency

Hz

50

4

Rated short-circuit current(valid value)

kA

20, 25

31.5

40

5

Rated ripe stable current (peak value)

kA

20, 25

31.5

40

6

Rated dynamic stable current(peak value)

kA

40

80

100

7

Rated power frequency tolerant voltage

Inter-polar /polar to ground

kV

42

Inter-fracture

kV

48

8

Rated lightening shock tolerance voltage

Inter-polar /polar to ground

kV

75

Inter-fracture

kV

85

9

Rated thermal time

s

4

10

Protection degree

 

1P2X

11

Outline dimensions

mm

1100*1200*2650 (see the note)

 

Note: dimensions for high current cabinet: 1200*1200*2650(Bypass bus bar cabinet outline demension1100 (1200*1900*2650(rated current above 2000A, width1200)

 

XGN2-12 4

 

Major parameters of vacuum breakers (table2)

 

No.

Name

Unit

Data

1

Rated voltage

kV

12

2

Rated current

A

630,1000,1250,2500,3150

3

Rated frequency

Hz

50

4

Rated short-circuit switch off current(valid value)

kA

20,25,31.5,40

5

Rated ripe stable current (peak value)

kA

20,25,31.5,40

6

Rated short-circuit switch on current (peak value)

kA

40,50,80,100

7

Rated peak value tolerance current (peak value)

kA

40,50,80,100

8

Rated power frequency tolerance voltage

kV

42/1min-Inter-polar polar to ground; 48/1min-Inter-fracture

9

Rated lightening shock tolerance voltage

kV

75-Inter-polar polar to ground; 85-Inter-fracture

10

Rated short-circuit last time

S

4

13

Rated capacitance groups switch off current

A

630

14

Rated back to back capacitance group switch off current

A

400

15

Times of rated short-circuit switch off current

time

30

16

Mechanical life

time

10000

 

Structure characteristics

 

  • This switchgear is case metal-enclosed structure. In accordance with the national standard GB3906 and international standardIEC298, protection degreeIP2X. The metal-enclosed structure effectively prevents short-circuit failure by intruders and human body from touching the electrical and operating components.
  • There are two structures of the cabinet :(1)steel angle welding (2)sectional bar assembling. Inside the cabinet, there are rooms for breaker, bus bars, cables and relay. Iron plates separate each room.

Breaker room is at the bottom of the cabinet with a pressure release channel. If there is any electric arc inside, gas pressure can be released through the channel.

Bus bar room is at the upper back of the cabinet. These lines are supported by epikote insulators (≥8000N). The main bus bar is connected with terminals of the upper insulation switch.

Cable room is at the lower back of the cabinet. Cables are fixed on the stands. This room serves as a communicator when the main connection line is designed to be communication-oriented.

No polar-to-polar or polar-to-ground insulation boards (or compound insulation materials) are used. When the air insulation distance between poles or from pole to ground is ≤125 mm, porcelain support insulators with a mechanical strength of ≥8000 N are applied. These measures ensure higher insulation strength and long-term stability.

The circuit breakers, both upper and lower insulation switches, grounding switches, and the interlock mechanisms between doors all adopt a forced mechanical locking system to fully meet the "five-prevention" safety requirements.

The unit supports dual-sided maintenance and does not require wall installation. Front access allows inspection of secondary components and maintenance of operating mechanisms, interlocks, transmission parts, and breakers, while rear access is provided for busbar and cable compartment maintenance. Interior lighting facilitates observation inside the cabinet, and copper grounding busbars beneath the doors are arranged parallel to the cabinet width.

The product meets the requirements of Condition I, making it suitable for environments with frequent freezing and minimal contamination.

XGN2-12 3

 

XGN2-12 7
XGN2-12 8

 

The structure of the typical scheme of the switchgear and the overall dimension

 

3
Diagram of the overall dimension of XGN2-12

 

1. bus bar room 2. pressure release channel 3. meter room
4. combined switch room 5. manual operation and interlock mechanics 6. the main switch room
7. electromagnetic or spring mechanics 8. grounding bus bars 9. cable room

 

FAQ

 

Q: 1. Do you have someone who handles after-sales service?

A: Yes, Service and complaint hotline works 24 hours for you.

Q: 2. Do you have any samples? How to obtain samples for free?

A: We can not provide the sample for free.

Q: 3. How to place your order?

A: Please contact us to place the order.

Q: 4. Are there any format and size requirements on the pattern for customization?

A: We can design according to your requirement.

 

Hot Tags: electrical ring main unit, China electrical ring main unit manufacturers, suppliers, factory, custom medium voltage switchgear, medium voltage air insulated switchgear, medium voltage switchgear, grounding medium voltage switchgear, mv medium voltage, lsc2b switchgear